DIN-A-MITE
Style D
Solid-State Power Controller
User’s Manual
Please consult this user’s manual when you place your new
DIN-A-MITE in service. It contains all the necessary
information to mount and wire it into the application. This
manual also contains all pertinent specifications and
semiconductor fusing recommendations. Please refer to
national and local electrical code safety guidelines whenever
you install electrical equipment.
This DIN-A-MITE product is capable of switching up to 100
amperes single-phase, at 600VÅ (ac) at 30°C (86°F),
depending on the model selected. It is electrically touch-safe
and includes standard back-panel mounting, on-board
semiconductor fuses, and a current transformer option for
external load current monitoring. Shorted SCR alarm output
option is also available.
The DIN-A-MITE Style D mounting footprint matches that of
an industry-standard 100-amperes mercury displacement
®
relay. This DIN-A-MITE is CE-approved, UL 508-listed and
®
C-UL .
1241 Bundy Boulevard, Winona, Minnesota USA 55987
Phone: +1 (507) 454-5300, Fax: +1 (507) 452-4507
0600-0025-0013 Rev F
Supersedes 0600-0025-0013 Rev. E
February 2007
Ordering Information
Unit Dimensions
203 mm (8.00 in) clearance for air
flow and bending radius
Side
DIN-A-MITE Style D, solid-state power controller
203 mm
(8.00 in)
Part Number
Phase
D D 1 0 - __ __ __ __ - __ __ __ __
13 mm
(0.50 in)
1
=
Single-phase, one
controlled leg
Cooling and Current Rating
0
=
Natural convection; current rating
80A @ 50°C (122°F)
Note: See the output rating curve
for the current rating at other
temperatures.
178 mm
(7.00 in)
185 mm
(7.28 in)
Line and Load Voltage
02
24
48
60
=
=
=
=
24 to 48VÅ(ac)
120 to 240VÅ(ac)
277 to 480VÅ(ac)
277 to 600VÅ(ac)
Input Control Signal
203 mm
(8.00 in)
C0
F0
F1
K1
K2
K3
=
=
=
=
=
=
4.5 to 32VÎ(dc) contactor
4 to 20mAÎ(dc) proportional
12 to 20mAÎ(dc) proportional
22 to 26VÅ(ac) contactor
100 to 120VÅ(ac) contactor
200 to 240VÅ(ac) contactor
203 mm (8.00 in) clearance for air flow and bending radius
Top
Grounding Screw
9.5 mm minimum diameter (3/8 in to 16 UNC)
Current Sensing or Alarm
66 mm
(2.58 in)
0
1
S
=
=
=
None
64 mm
(2.50 in)
Load current transformer
Shorted SCR alarm
User Manual Language
0
1
2
3
=
=
=
=
English
German
Spanish
French
239 mm
(9.41 in)
54 mm
(2.13 in)
Custom Options
00 Standard
Mounting
Footprint
=
ç
Note:
• Recommended fusing options to meet 200KA SCCR, type 1 and
2 approved. All other fuse combinations are defaulted to 5KA
SCCR per UL508A and NEC guidelines.
3
67 mm
(2.63 in)
Ó
Watlow part number:
0808-0096-0000
170N3437
67 mm
(2.63 in)
Bussmann part number:
61 mm
5
(2.38 in)
Output Rating Curve
13 mm
(0.50 in)
DIN-A-MITE Style D Natural Convection at 100% on
Allowance For No. 10 Fastener
Metric = M5
85
80
75
70
65
60
55
50
45
40
35
30
25
ç
WARNINGS:
Ó3
WARNING: Only authorized and qualified
personnel should be allowed to install and
perform preventive and corrective maintenance
on this unit. Failure to do so could result in
damage to equipment, and personal injury or
death.
WARNING: Hot surface, do not touch the heat
sink. Failure to follow this guideline could result
in personal injury.
0
5
10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100105
5
Current (Amperes) Into a Resistive Load
WATLOW DIN-A-MITE Style D User’s Manual
3
System Wiring Example
ç
Ó3
ç
Ó
WARNINGS:
Fuse Replacement
1 WARNING: Use National Electric (NEC) or other
country-specific standard wiring practices to install
and operate the DIN-A-MITE. Failure to do so may
result in damage to equipment and property,
and/or injury or loss of life.
ç
Ó
3
Ó
2 WARNING: Wiring examples show L2 in phase-to-
phase, 200VÅ(ac) and above configuration. In
phase-to-neutral, 100VÅ(ac) and above
applications, L2 is neutral and must not be fused
or switched. Failure to follow this guideline could
result in personal injury or death.
Ó
3
WARNING: Only authorized and qualified personnel
should be allowed to install and perform
preventive and corrective maintenance on this
unit. Failure to do so could result in damage to
equipment, and personal injury or death.
Ó4
WARNING: Do not use the DIN-A-MITE Vac-input
models with a temperature controller that includes
an RC snubber circuit across its output. Remove
the RC snubber circuit before placing the DIN-A-
MITE into service.
5
WARNING: Hot surface, do not touch the heat sink.
Failure to follow this guideline could result in
personal injury.
After removing all power, use a 7/16-inch nut driver to remove
fuse mounting nuts. Torque to 4.52 Nm (40 in-lb).
4
WATLOW DIN-A-MITE Style D User’s Manual
Single-Phase Output and Input Wiring
L1 L1 for all
voltages
ç
Limit Control
Contacts
(if required)
4 to 20mA input:
3
4
(+)
(-)
2
Ó
1
4.5 to 32VÎ (dc) input:
3
3
4
(+)
(-)
Semiconductor
Fuses
Ó
Ground lug supplied. Use
Thomas & Betts crimp tool
options below or equivalent.
Use 6 AWG copper conductor.
TBM 20S
TBM 25S
TBM 5
TBM 6
TBM 8
4
Ó
VÅ (ac) input
3
4
5
6
Alarm or Current Transformer Output
Alarm or Current Transformer Output
(Model Number-Dependent)
Open Heater
Alarm Adjust
TBM 60RS
Current Sensing Option
DD10 - _ _ _ _ - 1 _ _ _
2
5
6
On-board
Current
Transformer
Current Monitor
or Indication
Heater
Heater
Phase-to-phase
200VÅ (ac)
and above
Non-latching Alarm Option
DD10- _ _ _ _ - S _ _ _
On-Board
Triac
5
6
VÅ
1A
Alarm
L2
Neutral
Phase-to-neutral
100VÅ (ac) and above
The neutral must not be switched.
Indicator
Shorted SCR Alarm
The Watlow DIN-A-MITE alarm option provides an alarm output for shorted SCR conditions. A shorted SCR alarm is detected
when there is no command signal and a load current is detected. The alarm output is then energized. This is a non-latching
alarm.
Torque Procedure
1. While connecting the line and load wires, ensure that all wire strands are inside the connector. Do not allow loose wire
strands to hang out of the connector. Once you have installed the wire, torque these same connections to 9.0 to 10.1 Nm
(80 to 90 in-lb). Use a dial or digital-type torque wrench and hold the torque at 9.0 to 10.1 Nm (80 to 90 in-lb) for 30 seconds.
The 30-second hold allows the wire to settle, minimizing the wire cold flow.
2. Re-torque the same connections after 48 hours.
3. Develop a maintenance program to re-torque all load and line connections every three to six months.
NOTE: L1 and L2 terminals are 3/16-inch Allen head screws.
WATLOW DIN-A-MITE Style D User’s Manual
5
Declaration of Conformity
DIN-A-MITE® “D” Power Controller
Watlow Winona, Inc.
1241 Bundy Blvd.
Winona, MN 55987 USA
Declares that the following product:
Designation:
DIN-A-MITE® “D” Power Control
Model Numbers:
DD10 – (02, 24, 48 or 60)(C0, C1, C2, K1, K2, K3, F0 or F1) –
(0, C, D, H or S)(followed by any 3 numbers or letters.)
Power Control, Installation Category III, Pollution degree 2
24 to 600VÅ(ac)
Classification:
Rated Voltage:
Rated Frequency:
50 or 60 Hz
Meets the essential requirements of the following European Union Directives by using the relevant
standards shown below to indicate compliance.
89/336/EEC Electromagnetic Compatibility Directive
EN 61326:
1997 With A1:1998 – Electrical equipment for measurement, control and laboratory
use – EMC requirements (Industrial Immunity, Group 1 Class A Emissions)
EN 61000-4-2: 1996 With A1, 1998 – Electrostatic Discharge Immunity
EN 61000-4-3: 1997 – Radiated Field Immunity
EN 61000-4-4: 1995 – Electrical Fast-Transient / Burst Immunity
EN 61000-4-5: 1995 With A1, 1996 – Surge Immunity
EN 61000-4-6: 1996 – Conducted Immunity
EN 61000-4-11: 1994 Voltage Dips, Short Interruptions and Voltage Variations Immunity
EN 61000-3-2: 1995 With A1-3:1999 – Harmonic Current Emissions
EN 61000-3-3: 1995 With A1:1998 – Voltage Fluctuations and Flicker. See note 3.
Note 1:
Note 2:
Note 3:
Use of an external filter is required to comply with conducted emissions limits. See
page 7 for information and instructions.
A Line Impedance Stabilization Network (LISN) was used for conducted emissions
measurements.
To comply with flicker requirements, command signal models F0 and F1 may not be
used, and cycle time must be set greater than 4 seconds on C0, C1, C2 and K1, K2,
K3 models.
73/23/EEC Low-Voltage Directive
EN 50178:
1997 Electronic equipment for use in power installations.
Raymond D. Feller III
Name of Authorized Representative
Winona, Minnesota, USA
Place of Issue
General Manager
Title of Authorized Representative
December 2001
Date of Issue
Signature of Authorized Representative
6
WATLOW DIN-A-MITE Style D User’s Manual
Required External EMI Filters For DIN-A-MITE With More Than 6 A Loads
An external EMI filter must be used in conjunction with the
DIN-A-MITE for loads in excess of six amperes (6 A) at 150 to
250 kHz. Without a filter applied, the DIN-A-MITE does not
comply with the conducted emissions standard for loads more
than 6 A at 150 to 250 kHz.
çWARNING:
The tank filters specified may suppress desirable communications
carried on power lines in the 150 to 250 kHz region. The filters may
suppress carrier current such as that used for infant monitors and
medical alert systems. Verify that suppressed carrier current or other
desirable communications on power lines creates no hazard to people
or property. Failure to observe this warning could result in damage to
property, and injury or death for personnel.
Watlow has verified that two types of filters will suppress
electromagnetic interference (EMI) created by the DIN-A-
MITE power controller to within the CE requirements.
A tank filter supplied by Crydom or Watlow, installed across
the power lines, suppresses EMI on the power lines.
See Figures 1 and 2 below.
ÓWARNING:
See Table 1 for the correct filter.
All filter installation and wiring must be performed by qualified
personnel, and conform to local and national electrical codes. Failure
to observe this warning could result in damage to property, and injury
or death for personnel.
Description
Filter
Single-phase, 230VÅ(ac) 1F25
Crydom Watlow
Filter
14-0019
14-0020
Three-phase, 440VÅ(ac)
3F20
DIN-A-MITE No. 1
A
1
2
Table 1 — DIN-A-MITE EMI filters.
Breaker or
fused disconnect
A
B
1
Breaker or
fused disconnect
Heater
Filter
1
2
C
2
B
Heater
Filter
PE
DIN-A-MITE
PE
DIN-A-MITE No. 2
A protective earth (PE) connection
is required.
A protective earth (PE) connection
is required to minimize EMI.
Figure 1 — Tank filter, single-phase, 230VÅ(ac).
Figure 2 — Three-phase, 2-leg control using two (2) DIN-A-MITE D
controllers. Contactor input models (C and K) only.
WATLOW DIN-A-MITE Style D User’s Manual
7
Returns
• Call or fax your distributor or the nearest Watlow sales office for
best information about returns.
• To return directly to Watlow Winona in the U.S., first call or fax
Customer Service for a Return Material Authorization (RMA)
number telephone: +1 (507) 454-5300; fax: +1 (507) 452-4507).
• Put the RMA number on the shipping label, along with a written
description of the problem.
• A restocking charge of 20% of the net price is charged for all
standard units returned to stock.
Technical Assistance
If you encounter a problem with your Watlow controller, review your
configuration information to verify that your selections are consistent
with your application: inputs; outputs; alarms; limits; etc. If the
problem persists after checking the configuration of the controller, you
can get technical assistance from your local Watlow representative, or
in the U.S., dial +1 (507) 454-5300. For technical support, ask for for
an Applications Engineer.
Please have the following information available when calling:
• Complete model number
• All configuration information
• User’s Manual
The DIN-A-MITE Style D User’s Manual is copyrighted by Watlow,
Inc., © September 2004, with all rights reserved.
Warranty
The Watlow DIN-A-MITE is warranted to be free of defects in
material and workmanship for 36 months after delivery to the first
purchaser for use, providing that the units have not been misapplied.
Since Watlow has no control over their use, and sometimes misuse, we
cannot guarantee against failure. Watlow's obligations hereunder, at
Watlow's option, are limited to replacement, repair or refund of
purchase price, and parts which upon examination prove to be
defective within the warranty period specified. This warranty does not
apply to damage resulting from transportation, alteration, misuse, or
abuse.
8
WATLOW DIN-A-MITE Style D User’s Manual
|